10 MM INSULATED DOUBLE-WALL

Double-wall metal chimney insulated with 10 mm thick rock wool, internal wall made of steel type 1.4404 (AISI316L), thickness: 0.5 mm, 0.6 mm, 0.8 mm or 1 mm, and external wall made of stainless steel or copper.
Internal diameters with external wall made of steel: 80 mm – 300 mm.
Internal diameters with external wall made of copper: 80 mm – 300 mm.

APPLICATIONS

Evacuation of wet and dry smoke under positive and negative pressure, ventilation products, fumes, generators.

CERTIFICATES

Compliance certificate for factory production monitoring.

DIAMETERS PRODUCED
INTERNO80100
ESTERNO100120

OTHER DIAMETERS

DESIGNATION WITH GASKET

Chimney system EN 1856-1 : T200 – P1 – W – V2 – L50050 – O(20)
EN 1856-1/09 : Reference standard
T200 : Temperature class( 200°C )
P1 : Pressure class( 200Pa )
W : Condensate resistance ( W : wet – D : dry )
V2 : Corrosion resistance ( Yes )
L50 : Material specification ( A316L )
050 : Material thickness( 5/10 )
060 : Material thickness( 6/10 )
O : Sootfire resistance ( G=yes – O=no )

(20) : Distance to combustible material( in mm )

DESIGNATION WITHOUT GASKET

Chimney system EN 1856-1 : T600 – N1 – D – V2 – L50050 – G(130)
EN 1856-1/09 : Reference standard
T600 : Temperature class ( 600°C )
N1 : Pressure class ( 40Pa )
D : Condensate resistance ( W : wet – D : dry )
V2 : Corrosion resistance ( Yes )
L50 : Material specification ( A316L )
050 : Material thickness ( 5/10 )
060 : Material thickness ( 6/10 )
G : Sootfire resistance ( G=yes – O=no )
(130) : Distance to combustible material ( in mm )

DOWNLOAD